UL Recognized/Listed Class 2 Power Supply, 36 Through 288 Watt Models, 12VDC and 24VDC

C2240open_961r_800x500
class2dclinedrawing

Specifications and Ordering Information

Single Circuit, Dimmable Indoor/Outdoor Enclosure, UL Listed, File E471431, CSA Approved, Manual Reset Overload Protection
MODEL NUMBERINPUTOUTPUT


VACHzAMPS (Max.)VDCAMPS (Max.)Watts

361-12DCR12050/600.58123A36
362-12DCR-24024050/600.28123A36
363-12DCR-27727750/600.24123A36

481-24DCR12050/600.63242A48
482-24DCR-24024050/600.33242A48
483-24DCR-27727750/600.28242A48

601-12DCR12050/600.81125A60
602-12DCR-24024050/600.41125A60
603-12DCR-27727750/600.38125A60

961-24DCR12050/601.12244A96
962-24DCR-24024050/600.57244A96
963-24DCR-27727750/600.50244A96

Multiple Circuit, Dimmable Indoor/Outdoor Enclosure, UL Recognized, File E235322, Manual Reset Overload Protection
MODEL NUMBERINPUTOUTPUT


VACHzAMPS (Max.)VDCAMPS (Max.)WATTS
C2240-12DCR12050/602.2125A Per Circuit 4 x 60VA Class 2 Circuits240
C2240-24DCR12050/602.5244A Per Circuit 3 x 96VA Class 2 Circuits288
Above units available in 240 or 277V inputs. Order “-240” or “-277”. Manual Reset Overload Protection for each Class 2 Circuit.
Important – Do not interconnect output circuits.

Individual Circuit DC Power Supply Specifications
Description
24V Model Value
12V Model Value
Unit

Input Voltage120 / 240 / 277120 / 240 / 277Volts AC, 1 AMP Max.
Output Voltage24.0 +/-0.312.0 +/-0.3Volts DC
Output Current2A, 48W/4A, 96W3A, 36W/5A, 60WAmps
Current Limit2.5/4.5 +/-0.253.5/5.5 +/-0.25Amps
The following applies to all models
 DetailsUnit

Load Regulation2%Volts
Line Regulation5%Volts
Input Frequency50-60Hertz
Power Factor.85 Typical 
Efficiency80 Typical%
MTBF100,0001 Hours
Operating Environment (AMB)Minus 30 to +60Deg “C”
Function Surface Temp.-40 to +80 (25 C AMB)Deg “C”
Storage Temp.Minus 65 to +90Deg “C”
Humidity100 (Non Cond)%
Size11.25 x 3.37 x 3.25Inches
Shipping Weight7.0Pounds

 

APPROVALS – SINGLE CIRCUIT: UL Listed Class 2 Power Supplies, UL 1310, UL 1012 (File E471431)
MULTIPLE CIRCUIT: UL Recognized Sign Accessory, UL 48 (File E235322)
CONSTRUCTION – Indoor/Outdoor NEMA Type 3R Rainproof Enclosure
WALL MOUNTING – Conduit Access Class 1 Wiring Compartment
3 Year Limited Warranty

Compatible with forward phase dimmers designed specifically for magnetic or inductive circuits. See PDF for detailed application information.

Models and Specifications Subject to Change Without Notice